Add to Cart
The power feed module supplies the Power Rail with a voltage of 24 V DC and a maximum current of 4 A. In the event of a device fault or a wiring fault of any isolator on the Power Rail, the collective error messaging relay alerts the controller via a binary I/O point. This relay can be configured as normally-open or normally-closed. A green LED on the front of the device indicates the power state, and a red LED lights up during a fault condition. In the sense of functional safety (SIL) the device provides no dangerous failures. Thereby the safe condition of the supplied isolators must be defined as the de-energized state. Thus the device will not influence the safety calculation or the SIL value. This device is compatible with all versions of the Power Rail.
Technical Data
Supply |
||
---|---|---|
Connection |
terminals 11+, 12- |
|
Rated voltage |
20 ... 30 V DC |
|
Fusing |
5 AT/250 V AC |
|
Power dissipation |
≤ 1 W |
|
Output |
||
Connection |
Power Rail |
|
Output current |
max. 4 A |
|
Output voltage |
Ui ≥ rated voltage Ur = Ui - 0.6 V |
|
Fault signal |
relay output: NO contact |
|
Contact loading |
30 V AC/ 2 A / cos φ ≥ 0.7 ; 40 V DC/ 2 A |
|
Energized/De-energized delay |
approx. 20 ms / approx. 20 ms |
|
Indicators/settings |
||
Display elements |
LEDs |
|
Control elements |
DIP switch |
|
Configuration |
via DIP switches |
|
Labeling |
space for labeling at the front |
|
Directive conformity |
||
Electromagnetic compatibility |
|
|
|
Directive 2014/30/EU |
EN 61326-1:2013 (industrial locations) |
Conformity |
||
Electromagnetic compatibility |
NE 21:2017 |
|
Degree of protection |
IEC 60529:2001 |
|
Ambient conditions |
||
Ambient temperature |
-40 ... 70 °C (-40 ... 158 °F) |
|
Mechanical specifications |
||
Degree of protection |
IP20 |
|
Connection |
screw terminals |
|
Mass |
approx. 100 g |
|
Dimensions |
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 |
|
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
|
Data for application in connection with hazardous areas |
||
Certificate |
UL 22 ATEX 2853 X |
|
|
Marking |
|
Directive conformity |
|
|
|
Directive 2014/34/EU |
EN IEC 60079-0:2018+AC:2020 , EN IEC 60079-7:2015+A1:2018 , EN IEC 60079-15:2019 |
International approvals |
||
FM approval |
FM 22 US 0031 X |
|
|
Control drawing |
116-0160 |
UL approval |
E106378 |
|
CSA approval |
CoC 1051840 |
|
IECEx approval |
|
|
|
IECEx certificate |
IECEx UL 16.0051X |
|
IECEx marking |
Ex ec nC IIC T4 Gc |