Add to Cart
1-channel isolated barrier, 230 V AC supply, Dry contact or NAMUR inputs, Input frequency 1 mHz ... 5 kHz, 2 relay contact outputs, Start-up override, Configurable by keypad, Line fault detection (LFD), Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 40 mm, Number of channels: 1-channel, Trip relay, Start-up override, Rotation speed monitoring, Safety Integrity Level (SIL): SIL 2, Rated voltage: 230 V AC ± 10 %, Field device: NAMUR sensor, Field device [2]: volt-free contact
Technical Data
General specifications |
||
---|---|---|
Signal type |
Digital Input |
|
Functional safety related parameters |
||
Safety Integrity Level (SIL) |
SIL 2 |
|
Supply |
||
Connection |
terminals 23, 24 |
|
Rated voltage |
230 V AC ± 10 % |
|
Rated current |
18 mA |
|
Power dissipation/power consumption |
≤ 2 VA / 2 VA |
|
Input |
||
Connection side |
field side |
|
Connection |
Input I: intrinsically safe: terminals 1+, 3- |
|
Input I |
acc. to EN 60947-5-6 (NAMUR) |
|
|
Pulse duration |
> 50 µs |
|
Input frequency |
0.001 ... 5000 Hz |
|
Line fault detection |
breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA |
Input II |
startup override: 1 ... 1000 s, adjustable in steps of 1 s |
|
|
Active/Passive |
I > 4 mA (for min. 100 ms)/ I < 1 mA |
|
Open circuit voltage/short-circuit current |
18 V / 5 mA |
Output |
||
Connection side |
control side |
|
Connection |
output I: terminals 10, 11, 12 |
|
Output I, II |
signal, relay |
|
|
Contact loading |
253 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A |
|
Mechanical life |
5 x 107 switching cycles |
|
Energized/De-energized delay |
approx. 20 ms / approx. 20 ms |
Transfer characteristics |
||
Input I |
|
|
|
Measurement range |
0.001 ... 5000 Hz |
|
Resolution |
0.1 % of measured value , ≥ 0.001 Hz |
|
Accuracy |
0.1 % of measured value , > 0.001 Hz |
|
Measuring time |
< 100 ms |
|
Influence of ambient temperature |
0.003 %/K (30 ppm) |
Output I, II |
|
|
|
Response delay |
≤ 200 ms |
Galvanic isolation |
||
Input I/other circuits |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
|
Output I, II against eachother |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
|
Output I, II/other circuits |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
|
Start-up override/power supply |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
|
Indicators/settings |
||
Display elements |
LEDs , display |
|
Control elements |
Control panel |
|
Configuration |
via operating buttons |
|
Labeling |
space for labeling at the front |
|
Directive conformity |
||
Electromagnetic compatibility |
|
|
|
Directive 2014/30/EU |
EN 61326-1:2013 (industrial locations) |
Low voltage |
|
|
|
Directive 2014/35/EU |
EN 61010-1:2010 |
Conformity |
||
Electromagnetic compatibility |
NE 21:2006 |
|
Degree of protection |
IEC 60529:2001 |
|
Ambient conditions |
||
Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) |
|
Mechanical specifications |
||
Degree of protection |
IP20 |
|
Connection |
screw terminals |
|
Mass |
300 g |
|
Dimensions |
40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 |
|
|
Height |
119 mm |
|
Width |
40 mm |
|
Depth |
115 mm |
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
|
Data for application in connection with hazardous areas |
||
EU-type examination certificate |
TÜV 99 ATEX 1408 |
|
|
Marking |
|
Supply |
|
|
|
Maximum safe voltage |
253 V AC (Attention! Um is no rated voltage.) |
Input I |
terminals 1+, 3-: Ex ia |
|
|
Voltage |
10.1 V |
|
Current |
13.5 mA |
|
Power |
34 mW (linear characteristic) |
Input II |
terminals 13+, 14- non-intrinsically safe |
|
|
Maximum safe voltage |
40 V (Attention! The rated voltage can be lower.) |
Output I, II |
terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe |
|
|
Maximum safe voltage |
253 V (Attention! The rated voltage can be lower.) |
|
Contact loading |
253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load |
Certificate |
TÜV 02 ATEX 1885 X |
|
|
Marking |
|
Output I, II |
|
|
|
Contact loading |
50 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load |
Galvanic isolation |
|
|
|
Input I/other circuits |
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity |
|
|
|
Directive 2014/34/EU |
EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals |
||
FM approval |
|
|
|
Control drawing |
16-538FM-12 |
UL approval |
E223772 |
|
IECEx approval |
|
|
|
IECEx certificate |
IECEx TUN 03.0000 |
|
IECEx marking |
[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I |
Related Models:
KFU8-UFT |
KFD0-CS-Ex1.51P |
NBB8-18GM50-A2-V1 |
K-HM26-2M-261533 |
KFD0-CS-Ex2.50P |
NBB8-18GM50-E0 |
NBB15-U1-E2 |
KFD0-CS-Ex2.51P |
NBB8-18GM50-E0-V1 |
NBB1,5-5GM25-E2 |
KFD0-RO-Ex2 |
NBB8-18GM50-E2 |
NBB1,5-5GM25-E2-V3 |
KFD0-SCS-Ex1.55 |
NBB8-18GM50-E2-V1 |
NBB1,5-F79-E0 |
KFD0-SD2-Ex2.1045 |
NBB8-18GM50-E2-V1-M |
NBB1,5-F79-E2 |
KFD0-SD2-Ex2.1245 |
NBB8-18GM60-A2-V1 |
NBB15-U1-Z2 |
KFD0-TR-Ex1 |
NBB8-18GM60-US |
NBB5-18GM50-E2-V1 |
KFD0-CC-1 |
NBN3-8GM40-E2-V3 |
NBB15-30GM30-E2-V1 |
KFD0-HMS-16 |
NBN3-F25F-E8-V1 |
NBB15-30GM50-A2-V1 |
KFD0-RSH-1.4S.PS2 |
NBN40-U1K-N0 |
NBB15-30GM50-E2 |
KFD0-SD2-EX1.10100 |
NBN40-U4LK-N0 |
NBB15-30GM50-E2-M |
KFD0-SD2-EX1.1045 |
NBVB15-U1.Z2 |
NBB15-30GM50-E2-V1 |
KFD2-UT2-1 |
NCB5-18GM40-NO |
NBB15-30GM50-E2-V1-M |
KFD2-CD-1.32 |
NJ10-30GM-N-5M |
NBB8-18GM30-E2 |
KFD2-CD-EX1.32 |
NJ15-30GK-N |
NBB8-18GM30-E2-V1 |
KFD2-HMM-16 |
NJ2-12GK-SN |
NBB8-18GM60-A2-V1 |
KFD2-SH-EX1.T |
NJ2-12GM-N |
NJ4-12GK-SN |
KFD2-UT2-1 |
RD0-FB-EX4.COM |
NJ5-18GK-N |
KFD2-VR4-EX1.26 |
SC3,5-G-N0 |
NJ5-18GK-N-150 |
KFU8-UFC-1.D |
SC3,5-G-N0-5M |
NJ5-18GM-N |
V15-G-2M |
SC3,5-G-N0-6M |
NJ8-18GK-N |
Z 787 |
SJ3,5-N |
RD0-FB-EX4 |
Z787.H |
SJ3,5-S1N |
RD0-TI-Ex8.FF.* |
HIC2031 |
UPR-03 |
Z787.F |
Z787.H.F |
SJ3,5-N-BU |